Usable kilowatt-hours for backup, for bill shifting, or for both.
Battery capacity is quoted in kilowatt-hours, but what you actually need depends on the load you want to carry and for how long. This converts that into usable energy, allowing for the round-trip efficiency losses that mean stored energy is always less than energy put in.
What this returns at the defaults
Carrying a 2 kW backup load for 12 hours at 90% round-trip efficiency needs 26.7 usable kilowatt-hours. Add 8 kWh of evening peak shifting and the requirement becomes 35.6 kWh. Note that only the product of load and hours matters: 1 kW for 24 hours and 3 kW for 8 hours both come to the same 26.7 kWh.
Last updated . Data as of 23 August 2026.
Battery sizing model
Usable kilowatt-hours for backup, shifting, or both.
—Usable capacity needed
—For backup
—For bill shifting
Energy only. Surge rating is a separate check this model does not make.
HyreSolar does not sell batteries. Compare against usable capacity, not nameplate.
Usable kilowatt-hours is not the number on the box
The battery sizing calculator returns usable energy, which is what you need to compare against a product’s usable capacity rather than its nameplate. Manufacturers publish both and they are not the same. Always compare like with like.
Energy is only half the specification, and this tool models the other half not at all. A battery has an energy rating in kilowatt-hours and a power rating in kilowatts, and the power rating is what decides whether it can start your loads. Our research found manufacturers publishing wildly different surge figures, 185 LRA on one product, "up to 48 A LRA" on another, and nothing at all on a third. The exclusion that bites in a real outage is surge, not energy.
Sizing for a very long outage gets expensive quickly, and there is a floor on run time nobody publishes. Across the products we read, usable capacity divided by the manufacturer’s own maximum continuous output comes to roughly 1.2 to 1.3 hours. That is what a battery does at full output; carrying a small load for a long time is the other end of the same trade.
Under 15 kWhA short outage or a genuinely small protected load. Realistic for a fridge, lights, internet and a few outlets.
15 to 30 kWhThe common residential range. Enough for an overnight outage on a well-chosen critical load panel.
Over 30 kWhMultiple units. Check the unit-to-unit separation the residential code requires and where they are permitted to be installed.
How to use this calculator
Every input below is a number you can find, not one you have to guess. This is where each one comes from.
01
Decide what you are actually backing up
Not the house. A list of circuits. This is the single most important decision and it is made at quote time and then physically wired.
Where to find itWalk the house and write down what genuinely must run: refrigeration, some lighting, internet, a well pump, medical equipment, heating controls. Our critical load panel page explains why circuits move, not appliances.
02
Add up that load in kilowatts
The continuous draw of everything on the protected list running together, not the sum of every nameplate in the house.
Where to find itAppliance labels give watts. A fridge cycles rather than running constantly, so its average is well below its label. Be realistic: over-stating this input is the most common way people arrive at a battery they cannot afford.
03
Set the hours you want to carry it
How long an outage you are sizing for. Only the product of load and hours matters, so halving the load doubles the hours.
Where to find itYour own experience and your utility’s reliability record. Our outage statistics by state give the measured picture rather than an impression.
04
Add daily peak import if you want bill shifting
The kilowatt-hours you buy during expensive hours and could instead supply from storage charged earlier.
Where to find itA time-of-use bill shows consumption by period. If you are not on a time-varying tariff, leave this at zero, there is nothing to shift.
05
Set round-trip efficiency
The share of energy put in that comes back out. Ninety percent is a reasonable planning figure; the datasheet gives the real one.
Where to find itThe manufacturer’s datasheet states round-trip efficiency. Moving from 80% to 95% changes the requirement here from 30.0 kWh to 25.3.
How this calculator works
Backup energy
Backup load in kW × hours, divided by round-trip efficiency.
Bill-shift energy
Daily peak import in kWh, divided by round-trip efficiency.
Combine if you want both
The two add, because a battery cannot hold the same kilowatt-hour in reserve and spend it on arbitrage.
Then check power separately
This tool does not do it. Compare your largest starting load against the product’s surge rating.
A household protecting refrigeration, lighting, internet, a gas furnace’s controls and a few outlets, around 2 kW continuous, through an overnight outage, on a time-of-use tariff with 8 kWh of evening peak import.
Inputs
Backup load
2 kW continuous
Hours to carry
12
Raw backup energy
24 kWh
Round-trip efficiency
90%
Backup requirement
26.7 kWh usable
Daily peak import
8 kWh
Shift requirement
8.9 kWh usable
Result
35.6 kWh usable
For both jobs at once. If you only want backup, 26.7 kWh. Note the losses: 24 kWh of delivered energy needs 26.7 kWh of storage, and 8 kWh of shifted consumption needs 8.9. Round-trip efficiency is a real 11% tax on everything a battery does.
How the answer moves
One input changed at a time. Every figure is computed by the calculator on this page.
Situation
Backup need
Shift need
Both
Base case2 kW × 12 h, 8 kWh shift, 90% RTE
26.7 kWh
8.9 kWh
35.6 kWh
1 kW for 24 hours
26.7 kWh
8.9 kWh
35.6 kWh
3 kW for 8 hours
26.7 kWh
8.9 kWh
35.6 kWh
Efficient battery, 95% RTE
25.3 kWh
8.4 kWh
33.7 kWh
Less efficient, 80% RTE
30.0 kWh
10.0 kWh
40.0 kWh
The first three rows are identical, and that is the lesson: only the product of load and hours matters. Halving what you protect doubles how long you can protect it, which is a far cheaper lever than buying more storage.
What moves this number most
Ranked. A proposal can change any of these without saying anything untrue, so these are the inputs to check first.
1
What you choose to back up
The dominant input and the one entirely within your control. Cutting the protected load from 3 kW to 1.5 kW doubles your runtime for free. This decision is made when the quote is drawn and then physically wired, so it is hard to change later.
2
How long an outage you size for
Linear with energy. Twelve hours costs twice what six does. Check your utility’s actual reliability before sizing for a multi-day event.
3
Round-trip efficiency
A quiet 11% tax at the 90% default. Between 80% and 95% the requirement moves from 30.0 kWh to 25.3, which is close to a whole extra unit on some products.
4
Surge rating, which this model ignores entirely
The specification that actually determines whether a well pump or an air conditioner will start. Manufacturers publish it inconsistently: we found 185 LRA stated on one product, "up to 48 A LRA" on another, and no figure at all on a third.
5
Where the battery is allowed to go
The residential code restricts placement, requires not less than three feet between units, sets clearances from doors and windows and imposes construction requirements on the enclosing space. Establish location before capacity.
A whole-home backup is a much larger and more expensive proposition than most people intend, and at least one manufacturer guide forbids it outright for its product. Back up circuits, not a building.
Adding up nameplate ratings instead of realistic loads
A refrigerator cycles rather than running continuously, so its average draw is far below its label. Summing labels produces a battery specification nobody needs.
Comparing usable kWh against nameplate kWh
Manufacturers publish both and they differ. This tool returns usable energy, so compare it against a product’s usable figure or you will undersize.
Ignoring the power rating
Energy tells you how long; power tells you whether it starts at all. A battery with ample kilowatt-hours can still fail to start a well pump. Ask for the surge rating in writing and check it against your largest motor load.
Assuming you can have backup and arbitrage from the same kilowatt-hours
You cannot. Energy held in reserve for an outage is energy not available to shift, which is why this tool adds the two requirements rather than taking the larger.
Deciding capacity before deciding location
The code restricts where storage may go and requires separation between units. A capacity that needs three units may not have anywhere compliant to put them.
Important: this is a planning estimate
Energy only. This model says nothing about the power or surge rating, which is what decides whether your loads will start.
Returns usable kilowatt-hours. Compare against a product’s usable capacity, not its nameplate.
Assumes the battery starts full and that you can choose what it powers.
Does not model depth of discharge limits, reserve settings, degradation over time or temperature derating.
Does not check where the code permits the storage to be installed, or how many units fit there.
Questions this calculator answers
What size home battery do I need?
Multiply the backup load you want to carry by the hours you want to carry it, then divide by round-trip efficiency. A 2 kW load for 12 hours at 90% efficiency needs 26.7 usable kilowatt-hours. Add your daily peak import separately if you also want to shift consumption off expensive hours.
Why do 1 kW for 24 hours and 3 kW for 8 hours give the same answer?
Because only the product of load and hours determines energy. Both are 24 kilowatt-hours of delivered energy and both need 26.7 kWh of usable storage at 90% efficiency. This is why reducing what you back up is the cheapest way to extend how long you can back it up.
What is round-trip efficiency and why does it increase the requirement?
It is the share of energy put into the battery that comes back out; the rest is lost to heat in charging and discharging. At 90% you need 26.7 kWh of storage to deliver 24 kWh of useful energy. It is a real tax on everything a battery does, and the datasheet gives the figure for your product.
Is usable capacity the same as the number on the box?
No. Manufacturers publish a nameplate capacity and a usable capacity and they differ, because a battery is not run to absolute empty. This tool returns usable kilowatt-hours, so compare it against the usable figure on the datasheet or you will undersize.
Will a big enough battery start my air conditioner or well pump?
Not necessarily, and this calculator cannot tell you. Starting a motor needs surge power, which is a separate specification from energy. Manufacturers publish it inconsistently, we found one stating 185 LRA, another saying "up to 48 A LRA" and a third publishing nothing. Ask for the figure in writing and check it against your largest motor.
How long will a battery run my house?
No manufacturer publishes a run time, because it depends entirely on what you connect. What we can tell you from the datasheets is that usable capacity divided by a product’s own maximum continuous output comes to roughly 1.2 to 1.3 hours across the products we read. That is the floor, at full output.
Can one battery do backup and bill shifting at the same time?
Only by splitting its capacity. Energy held in reserve for an outage is not available to shift, which is why this tool adds the two requirements rather than taking whichever is larger. If you want both fully, you need both amounts.
Should I size for a multi-day outage?
Check your utility’s actual reliability first. Sizing for a rare event is expensive, and the alternative for very long outages is usually a generator, which brings its own risks, the federal record includes at least 1,332 carbon monoxide deaths between 2004 and 2021. Our comparison page covers that trade honestly.
Does the code limit where I can put a battery?
Yes, substantially. Residential storage must be listed and labelled to a storage standard, individual units must be separated by not less than three feet unless the listing says otherwise, there are clearances from doors and windows, and enclosing walls and ceilings carry construction requirements. Settle the location before the capacity.
Is a battery worth it financially?
That depends on your export credit, not on the battery. Under full retail net metering, storing a kilowatt-hour and exporting it are worth the same and the arbitrage value is zero. Under net billing there is a real gap. Our net billing calculator puts a ceiling on it so you can compare against the quoted cost.
The research behind these numbers
Every assumption in this calculator is argued from primary sources somewhere in our research library. These are the pages that matter for this one.
The critical load panelWhich circuits actually run in an outage, why circuits move rather than appliances, and the code requirements on where storage goes.
Battery backup versus a generatorWhy surge and not energy is the exclusion that bites, and the federal carbon monoxide record of the alternative.
Home battery chemistryWhat manufacturers do and do not publish. One major product has no chemistry row on its datasheet at all.
Power outage statistics by stateHow long outages actually last where you live, computed from federal data rather than impression.
Primary-source research, data analysis and fact checking
We are a research desk, not a sales floor. We read the statute, the tariff, the code section, the federal filing or the manufacturer data sheet ourselves, and we publish the figure with the document it came from and the date we retrieved it. Where a number cannot be traced to a primary source, we publish the shorter page and say what we could not verify. That rule has cost us whole sections, and it is the reason the rest can be trusted.
160
primary sources read and cited
220
figures with a retrieval date
115
federal and state government sources
66
researched pages published
How this desk works
Primary sources only. Statutes from the legislature’s own publishing system, federal data from the agency that collects it, code text from the adopted edition, manufacturer claims from the data sheet. We do not cite an article that cites a source; we go and read the source.
Every figure carries its provenance. A named document and the date we retrieved it, so you can check it and so you know how old it is. Retrieval dates are not decoration: an EIA rate from May is a different fact from an EIA rate from August.
We publish what we could not verify. Every research page carries a section naming the things we tried to establish and could not, and why. A paywalled standard, a state website that refused the request, a manufacturer that publishes no figure at all.
We separate measurement from modelling from our own reasoning, and label which is which on the page. A laboratory measurement, an assumption inside a modelling tool and our own inference are three different kinds of claim and they are never presented as one.
We do not sell solar, and we take no payment for placement, ranking or a favourable mention. Nobody buys a position on this site.
Data as of 23 August 2026.
Authorship on this site is organisational: the analysis belongs to the desk rather than to a named individual,
and we do not publish credentials we do not hold. Our
editorial policy sets out how we source, date and correct what we publish.